Home    Key and supplementary comparisons    Calibration and Measurement Capabilities - CMCs
The BIPM key comparison database
Refine your search
CMC AREA
CMCs General Physics (11)
PHYSICS
AC voltage, current, and power (11)
AC voltage up to 1000 V: sources (1)
AC voltage up to 1000 V: meters (1)
AC power and energy: three phase, active power (1)
AC power and energy: three phase, reactive power (1)
AC power and energy: three phase, apparent power (1)
AC power and energy: single phase (frequency below or equal to 400 Hz), active power (1)
AC power and energy: single phase (frequency below or equal to 400 Hz), reactive power (1)
AC power and energy: single phase (frequency below or equal to 400 Hz), apparent power (1)
AC voltage: AC-DC transfer difference at low voltage (1)
AC voltage: AC-DC transfer difference at medium voltage (1)
AC voltage: AC-DC transfer difference at higher voltage (1)
GEOGRAPHIC LOCATION
COOMET (11)
Belarus (11)
Result of the search
Your query 'belarus' produced 11 results New search

 
Belarus, BelGIM (Belarussian State Institute for Metrology)
Complete CMCs in Electricity and Magnetism for Belarus (.PDF file)
AC voltage: AC-DC transfer difference at low voltage. Thermal converter with amplifier, AC-DC transfer standard, 0.002 V to 0.5 V
Relative expanded uncertainty (k = 2, level of confidence 95%) in µV/V: 24 to 221
Comparison
Frequency: 10 Hz to 1 MHz
Approved on 20 December 2013
Internal NMI service identifier: COO-EM-BELGIM 5001
Uncertainty table
 
AC voltage: AC-DC transfer difference at medium voltage. Thermal converter, AC-DC transfer standard, 0.5 V to 5 V
Relative expanded uncertainty (k = 2, level of confidence 95%) in µV/V: 24 to 144
Comparison
Frequency: 10 Hz to 1 MHz
Approved on 20 December 2013
Internal NMI service identifier: COO-EM-BELGIM 5002
Uncertainty table
 
AC voltage: AC-DC transfer difference at higher voltage. Thermal converter with ranger resistor, AC-DC transfer standard, 5 V to 1000 V
Relative expanded uncertainty (k = 2, level of confidence 95%) in µV/V: 24 to 142
Comparison
Frequency: 10 Hz to 1 MHz
Approved on 20 December 2013
Internal NMI service identifier: COO-EM-BELGIM 5003
Uncertainty table
 
AC voltage up to 1000 V: sources. Multifunction calibrator, 0.002 V to 1000 V
Relative expanded uncertainty (k = 2, level of confidence 95 %) in µV/V: 25 to 598
AC-DC transfer standard
Frequency: 10 Hz to 1 MHz
Approved on 20 December 2013
Internal NMI service identifier: COO-EM-BELGIM 5004
Uncertainty table
 
AC voltage up to 1000 V: meters. AC voltmeter, multimeter, 0.002 V to 1000 V
Relative expanded uncertainty (k = 2, level of confidence 95 %) in µV/V: 25 to 598
AC-DC transfer standard
Frequency: 10 Hz to 1 MHz
Approved on 20 December 2013
Internal NMI service identifier: COO-EM-BELGIM 5005
Uncertainty table
 
AC power and energy: single phase (frequency below or equal to 400 Hz), active power. Power and energy meter, power converter, wattmeter,power comparator, 0 kW to 57.6 kW
Relative expanded uncertainty (k = 2, level of confidence 95%) in µW (VA)-1: 150 to 300
Direct comparison
Frequency: 45 Hz to 65 Hz
Voltage: 30 V to 480 V
Current: 0.005 A 120 A
Phase shift: -90 ° to 90 °
Approved on 15 March 2016
Internal NMI service identifier: COO-EM-BELGIM 7001
Uncertainty table
 
AC power and energy: three phase, active power. Power and energy meter, power converter, wattmeter,power comparator, 0 kW to 76.8 kW
Relative expanded uncertainty (k = 2, level of confidence 95%) in µW (VA)-1: 180 to 200
Direct comparison
Frequency: 15 Hz to 70 Hz
Voltage: 30 V to 480 V
Current: 0.005 A to 160 A
Phase shift: -180 ° to 180 °
Approved on 15 March 2016
Internal NMI service identifier: COO-EM-BELGIM 7002
Uncertainty table
 
AC power and energy: single phase (frequency below or equal to 400 Hz), apparent power. Power and energy meter, power converter, wattmeter, power comparator, 0 kVA to 76.8 kVA
Relative expanded uncertainty (k = 2, level of confidence 95%) in µVA (VA)-1: 150 to 300
Direct comparison
Frequency: 15 Hz to 70 Hz
Voltage: 30 V to 480 V
Current: 0.005 A to 160 A
Phase shift: -180 ° to 180 °
Approved on 15 March 2016
Internal NMI service identifier: COO-EM-BELGIM 7003
Uncertainty table
 
AC power and energy: three phase, apparent power. Power and energy meter, power converter, wattmeter, power comparator, 0 kVA to 76.8 kVA
Relative expanded uncertainty (k = 2, level of confidence 95%) in µVA (VA)-1: 150 to 300
Direct comparison
Frequency: 15 Hz to 70 Hz
Voltage: 30 V to 480 V
Current: 0.005 A to 160 A
Phase shift: -180 ° to 180 °
Approved on 15 March 2016
Internal NMI service identifier: COO-EM-BELGIM 7004
Uncertainty table
 
AC power and energy: single phase (frequency below or equal to 400 Hz), reactive power. Power and energy meter, power converter, wattmeter, power comparator, 0 kvar to 76.8 kvar
Relative expanded uncertainty (k = 2, level of confidence 95%) in µvar (VA)-1: 150 to 300
Direct comparison
Frequency: 15 Hz to 70 Hz
Voltage: 30 V to 480 V
Current: 0.005 A to 160 A
Phase shift: -180 ° to 180 °
Approved on 15 March 2016
Internal NMI service identifier: COO-EM-BELGIM 7005
Uncertainty table
 
AC power and energy: three phase, reactive power. Power and energy meter, power converter, wattmeter, power comparator, 0 kvar to 76.8 kvar
Relative expanded uncertainty (k = 2, level of confidence 95%) in µvar (VA)-1: 150 to 300
Direct comparison
Frequency: 15 Hz to 70 Hz
Voltage: 30 V to 480 V
Current: 0.005 A to 160 A
Phase shift: -180 ° to 180 °
Approved on 15 March 2016
Internal NMI service identifier: COO-EM-BELGIM 7006
Uncertainty table