Home    Key and supplementary comparisons    Calibration and Measurement Capabilities - CMCs
The BIPM key comparison database
Refine your search
CMC AREA
CMCs General Physics (3)
PHYSICS
Impedance up to the MHz range
Dimensional metrology
DC voltage, current, and resistance (3)
DC voltage sources: single values (3)
CHEMICAL ANALYTE
zinc
phenanthrene
GEOGRAPHIC LOCATION
SIM (3)
Mexico (3)
Result of the search
Your query 'cenam' produced 3 results New search

 
Mexico, CENAM (Centro Nacional de Metrologia)
Complete CMCs in Electricity and Magnetism for Mexico (.PDF file)
DC voltage sources: single values. Solid state voltage standard, 1 V
Relative expanded uncertainty (k = 2, level of confidence 95%) in µV/V: 0.3
Ratio technique from 1.018 V to 1 V via a DVM
Room temperature: 23 °C
Ambient pressure: 81 kPa
Approved on 28 April 2011
Internal NMI service identifier: CENAM/E011-003-01
 
DC voltage sources: single values. Solid state voltage standard, 1.018 V
Relative expanded uncertainty (k = 2, level of confidence 95%) in µV/V: 0.3
Differential measurement using a redundant design
Room temperature: 23 °C
Ambient pressure: 81 kPa
Approved on 28 April 2011
Internal NMI service identifier: CENAM/E011-003-02
 
DC voltage sources: single values. Solid state voltage standard, 10 V
Relative expanded uncertainty (k = 2, level of confidence 95%) in µV/V: 0.3
Ratio technique from 1.018 V to 10 V via a DVM and a resistive divider
Room temperature: 23 °C
Ambient pressure: 81 kPa
Approved on 28 April 2011
Internal NMI service identifier: CENAM/E011-003-03