Refine your search |
|
CMC AREA |
|
|
|
|
PHYSICS |
|
|
|
|
CHEMICAL ANALYTE |
|
|
|
|
GEOGRAPHIC LOCATION |
|
|
|
|
|
 |
Result of the search |
|
| | | Mexico, CENAM (Centro Nacional de Metrologia) | |  | Complete CMCs in Electricity and Magnetism for Mexico (.PDF file)
|  | |
| AC power and energy: single phase (frequency <= 400 Hz, active power). Multifunction calibrators, 60 W to 2.4E+03 W | | Relative expanded uncertainty (k = 2, level of confidence 95%) in µW/VA: 100 | | Direct comparison | | Voltage: 120 V, 240 V | | Current: 1 A, 10 A | | Power factor: 1 to 0.5, inductive or capactive | | Frequency: 60 Hz | | Approved on 05 January 2012 | | Internal NMI service identifier: CENAM/E012-001B-CC |
| | | AC power and energy: single phase (frequency <= 400 Hz, active power). Power meter, 0 W to 6E+04 W | | Relative expanded uncertainty (k = 2, level of confidence 95%) in µW/VA: 20 to 30 | | Direct comparison | | Voltage: 120 V, 240 V, 480 V, 600 V | | Current: 0.25 A to 100 A | | Power factor: 1 to 0, inductive or capacitive | | Frequency: 60 Hz | | Approved on 05 January 2012 | | Internal NMI service identifier: CENAM/E012-001-01 | | Uncertainty table |
|